HB1522 Irradiation cross-linked silicone rubber self-fusing tape

Specification 1: 0.8mm (thickness) × 50mm (width) × 5m (length)

Specification 2: 0.8mm (thickness) × 50mm (width) × 5m (length)

Color: red, yellow, green, gray, blue, black

Appearance: colored silicone rubber band

Working conditions: -60℃~200℃

Packing specification: 50 rolls/carton

HB1522 radiation cross-linked silicone rubber self-fusing tape is mainly used for insulation protection of power bus bars, bus bars, and special-shaped bare conductors in substations. It can also be used for reinforced insulation protection of UHV overhead bare wires and bare conductors.

 

product information

Specification 1: 0.8mm (thickness) × 50mm (width) × 5m (length)

Specification 2: 0.8mm (thickness) × 50mm (width) × 5m (length)

Color: red, yellow, green, gray, blue, black

Appearance: colored silicone rubber band

Working conditions: -60℃~200℃

Packing specification: 50 rolls/carton

 

Product Features

1. Unaffected by the weather, it has anti-oxidation, anti-ozone and anti-ultraviolet effects.

2. It can insulate and protect the charged body of any shape without a free end, which has strong practicability.

3. All indexes are better than traditional heat-shrinkable materials, especially suitable for comprehensive insulation protection of substations.

4. Convenient and fast, no need for open flame heating, no need for special tools, no need to remove screws, suitable for construction in various temperature environments, short time, and can shorten the power outage time.

5. Convenient maintenance, only glues itself, easy to peel off from the entangled material, easy to test or repair, and reduce operation time and cost.

6. Special performance: damping and shock absorption, anti-mechanical vibration, as well as anti-corona, anti-arc, anti-flashover.

 

Scope of application

1. Insulation protection of any live bare conductors, such as outdoor busbar bridges, indoor switch busbars, cabinet busbars, handcart busbars, equipment electrical contacts (screw connection bushings, etc.), various types of clamps, cable head terminals, ring network cabinets Internal bus bar, etc.

2. Large-scale cable insulation and irregular conductor insulation protection.

3. Insulation protection in the high and low temperature environment of the power system in mines, oil fields, chemical industries, etc. where open flames cannot be used.

4. Insulation protection of electrical appliances.

 

Instructions

Keep the surface and hands clean during operation. Stretching and winding all the way, the end stretches and fits the body for compaction. Finally, the whole is compacted by hand.


Test items

Typical parameters

Test based on

Tensile Strength

3.5MPa

GB/T 528-2009

Elongation at break

1000%

GB/T 528-2009

Corrosion of metals

Class A


Cold tolerance

0.5


Volume resistivity

1×1014Ω·cm

GB/T 1692-2008

Breakdown strength

28kV/mm

GB/T 1695-2005

Dielectric constant

2-3

GB/T 1693-2007