Product Model Comparison Table

High pressure heat shrink finger cot YEVA-MB

Working temperature: -55℃~+105℃

Shrinking temperature: 70℃~130℃

Anti-tracking, anti-ultraviolet

Coated with weather-resistant sealant, excellent sealing performance

Applied to 10~36kV voltage grade cable terminal

Standard color: iron red

product description:

The heat-shrink high-pressure finger cot is made of a specially formulated radiation cross-linked polyene light material, coated with anti-electric carbon trace and weather-resistant sealant. It has excellent insulation, UV resistance and weather resistance, and is widely used in indoor and outdoor terminals of medium voltage cables.

Features:

Working temperature: -55℃~+105℃

Shrinking temperature: 70℃~130℃

Anti-tracking, anti-ultraviolet

Coated with weather-resistant sealant, excellent sealing performance

Applied to 10~36kV voltage grade cable terminal

Standard color: iron red


SpecificationLarge end inner diameter (mm)Finger inner diameter (mm)Length before/after shrinking ±10%Wall thickness after shrinking ±10%
Supply sizeAfter shrinkingSupply sizeAfter shrinkingTotal lengthFinger lengthMain bodyFinger
320-60/246024258175/17038/403.02.5
330-80/3880383515200/21050/553.53.3
340-110/48110504618210/23055/553.63.3
350-125/55125555720220/24058/603.73.3
360-140/68140706426250/27060/653.83.5


ProjectTest MethodsTypical data
Tensile StrengthASTM D 2671≥10Mpa
Elongation at breakASTM D 2671≥300%
Thermal aging tensile strengthASTM D 2671(120°C/168 hours)≥8Mpa.
Thermal aging elongation at break≥250%
Breakdown strengthIEC 243≥20KV/mm
Electric carbon tracking resistanceASTM D 2303/3.75kV/1hrpass through
Volume resistivityIEC 93≥10^13Ω.cm
Water absorptionISO 62≤0.5%